If the pool water circulation ….
News
July 14, 2022
If the pool water circulation ….

If the pool water circulation pump stops due to an unforeseen problem or for maintenance, and the chemical feed equipment continues to add chlorine-based disinfectant and acid into the line, the two chemicals may react to form hazardous chlorine gas. Chlorine gas produced this way displaces pool water in the line, with the amount being proportional to the length of time the circulation pump is out of service and the chemical feeders are operating.

When the pool water circulation pump is restarted and proper water circulation is restored, the chlorine gas is pushed through the line into the pool area where swimmers and staff may be exposed to hazardous levels. This scenario repeats itself several times each year in various locations, which prompted the American Chemistry Council and a group of public health and swimming pool industry representatives to develop a free YouTube training video to help prevent these unfortunate events. Their fact sheet is based on information and guidance offered in the video.

LEVELS OF ELECTRICAL INTERLOCK PROTECTION

Electrical interlock protection ensures that if the pool pump is disabled or loses prime/no flow situation, or there is any other loss or reduction of flow in the circulation system, the chemical feed equipment will also be disabled, avoiding the production of chlorine gas in the line. This shall be accomplished through an electrical interlock consisting of at least two of the following: 1. Circuit Breaker Design (Basic): Ensure the circulation pump and the chemical feed equipment are on the same electrical circuit. If the circuit powering the pump is tripped, power to the chemical feeders is also lost and there will be no injection of chemicals.

2. Pump or Filter Control. This method uses a basic three-way pump control panel with an AUTO/ OFF/HAND configuration. Ensure the chemical feed equipment is connected to only the AUTO function for pump control. The pump should be backwashed only in HAND mode. If the switch is in the OFF or HAND mode, power to the chemical feeders is also lost and there will be no injection of chemicals. For systems using regenerative filtration or sand filtration with automatic backwash control, there are common relays that can be programmed to disable chemical automation during bump or backwash sequences. Most variablespeed drives can be programmed to enable or disable automated chemical controllers. Never connect chemical feed systems directly to power, or “hot,” which bypasses the pump electrical interlock.

3. Float or Centrifugal Flow Switch. A float or centrifugal flow switch can be incorporated into the sample stream of the chemical controller, which samples water flow. When the sample stream loses flow, the switch signals the controller to stop the chemical feed.

4. Flow Switch or Electronic Flow Meter. A flow switch or electronic flow meter with signaling capabilities can be used in the main circulation system’s return stream of water, indicating there is flow through the main system.

PRECAUTIONS

• A flow switch could fail and send a false indication of water flow when there is none.

• The flow switch should only be used as a backup to the electrical interlock between the water circulation pump and chemical feed system.

• The safety switch system should be installed and maintained according to the manufacturer’s instructions and not modified or bypassed in any way.

• Conduct an initial challenge test upon installing an interlock system.

• Conduct monthly challenge tests, including a backwash cycle at least once per month, to ensure the proper operation of the interlock safety switch, sensors, and alarms.

• Basic interlock designs only react to electrical incidents, such as loss of power, and not to an inherent loss of water flow, which could be caused by something other than the loss of power.

• Basic protection can be lost if someone unknowingly unplugs the chemical feeder from the controlled circuit and plugs it into another circuit.

• An alarm should be activated whenever the chemical feeder is disabled through the interlock system to alert staff to evacuate the pool.

• Maintain proper labeling of all system components.

• Keep all signs, labels, and placards up to date and legible.

• Use safety signs as reminders to take action under certain circumstances.

• Follow OSHA h a z a r d communication plan requirements, including developing an emergency action plan.

POOLSTAFF BEST PRACTICES

1. The aquatic venue should be closed and all bathers removed from the pool and deck whenever maintenance work is to be performed on the circulation and chemical systems.

2. The pool and deck area should be cleared immediately when:

• A flow sensor detects no flow in the system.

• An unexpected or manual deactivation of the circulation pump occurs.

• The interlock system is activated, indicating a problem with the flow system.

3. Bathers should not be allowed back into the aquatic venue until the cause of the interruption is understood and the condition is corrected.

• The system should operate correctly for at least 5 minutes before bathers return to the water.

• Water should be tested for proper pH and free chlorine levels before bathers return to the water.

• Train staff to recognize highrisk scenarios that could lead to chlorine gas exposure, such as when water circulation ceases and when the electrical interlock and safety switch failure alert system is activated.

Each year dozens of visitors to aquatic facilities are accidentally exposed to unintentionally produced chlorine gas. These exposures result from a failure of the electrical interlock between the chemical feed equipment (usually involving acid and sodium hypochlorite bleach) and the water circulation pump. This video presents steps that aquatic staff can take to reduce the risk of these exposures.

LATEST NEWS
Idaho ends state mandated pool inspections
News
Idaho ends state mandated pool inspections
New law takes health safety regulatory power away from Idaho Dept. of Health
May 14, 2025
By Marcelle Dibrell Starting July 1, 2025, public swimming pools across Idaho will no longer be subject to state-mandated health inspections, the resu...
this is a test
Service starts with water sanitation
News
Service starts with water sanitation
May 14, 2025
Maintaining proper disinfection levels is the core of pool and spa maintenance. And while a pool and spa pump is often described as the heart of the p...
this is a test
News
Drowning prevention bills failed in Florida
May 14, 2025
A pair of Florida bills that would have tightened anti-drowning measures for the state’s residential pools failed in subcommittee meetings this April....
this is a test
Olympian gets 10 replacement medals
News
Olympian gets 10 replacement medals
May 14, 2025
Olympic swimmer Gary Hall Jr. lost all of his medals in the 2025 Los Angeles fires. When the house he was renting in the Pacific Palisades went up in ...
this is a test
News
Nominate the next PHTA superstar
May 14, 2025
The Pool & Hot Tub Alliance wants your help recognizing the best of the best in our industry. Do you know someone who goes above and beyond — on the j...
this is a test
News
United Chemical launches bromate study
May 14, 2025
United Chemical, a premier provider of specialty pool chemicals, is launching a new study that will examine a possible byproduct that may result from ...
this is a test
Read Our Newsletter
ePaper
coogle_play
app_store
Free Subscription
View Current Print Ads
Educational Announcements
Aquatic Training Institute

Educational Leverage

Foundation For Pool Industry Education

Locey Pool

Pool Chemistry Training Institute

Pool & Hot Tub Alliance

Portofino University

Underwater Pool Masters
Trade Show Dates
  • The International Pool Spa Patio Expo
    Nov. 12-14, Dallas, Texas
  • The Pool and Spa Show
    Jan. 28-30, Atlantic City, New Jersey
  • 35th Annual National Plasterers Conference
    Feb. 26-28, Lake Buena Vista, Florida
  • The Southwest Pool and Spa Show
    Feb. 4-8, Houston, Texas
  • The Western Pool and Spa Show
    Feb. 6-8, Long Beach, California
Books to Order
About Us Terms of Use Privacy Policy
We use cookies to ensure that our website gives you the best experience possible. By continuing to use this website, you agree to this use of cookies.OK